Main functions
- Transmission and reception of up to 32 RP and SIPS commands over
- Multiplexed and/or dedicated FOCL channels
- Coupling with multiplexers in accordance with C37.94 and/or E1 standard
- Relaying of transit commands
- Time synchronization of the transmitter and receiver with an accuracy of 2 ms
- Capability to operate in a bidirectional ring arrangement
- Connection to a multiplexer or remote transceiver via two independent channels
- Continuous monitoring of all nodes and units
- Including input circuits of transmitter and relays of binary outputs
- Registration of all events in a non-volatile event log
- Connection to the substation’s SAS under the IEC 60870-5-101 and IEC 60870-5-104 protocols
Distinctive features
- Simultaneous transmission/reception of all commands
- Communication range 1...200 km
- Length of wave and communication range are determined by the by the SFP module used
- Continuous monitoring of the communication channel
- Issuing of warnings and tripping of alarms when the communication channel is lost
Basic performance data
types of optical fiber
|
- single-mode 9/125 μm
- multimode 50/125 μm
|
optical connector type
|
LC
|
command transmission time:
- multiplexed channels (C37.94)
- FOCL
|
|
accuracy of event time measurement
|
2 ms
|
power consumption
|
50 W
|
weight, up to
|
13 kg
|
overall dimensions (WxHxD)
|
482х266х370 mm
|
Hardware versions*
- Duplex transceiver for 32 commands over one or two multiplexed C37.94 channels
- Duplex transceiver for 32 commands over one or two FOCL channels
- Duplex transceiver for 32 commands over FOCL and multiplexed C37.94 channel
Power supply
110 VDC, 220 VDC
Operating temperature range
0...+45°C
* Determined by the range of digital channel blocks.