Category: Vibration digital equipment
BIPM is designed to insure intrinsic safety on a single (dual, BIPM-5K) AC/DC circuit. Barriers are typically used with different sensors driven in alarm and protection systems (in hazardous areas, classification 0,1,2, where flammable mixtures, of the categories IIA, group T1-T5 may be formed).
BIPM limit voltage and current in hazardous area circuits.
Parameter | BIPM-5/BIPM-5K | BIPM-15/BIPM-15K | BIPM-24/IBS-24K |
Operating input voltage | 5.5 VDC | 16 VDC | 26 VDC |
Nominal input voltage | 5 VDC | 15 VDC | 24 VDC |
Max. input voltage (Um) | 250 V | ||
Max. output voltage (U0) | 5.88 VDC | 18.9 VDC | 26.25 VDC |
Max. output current (I0) | 410 mADC | 540 mADC | 510 mADC |
Max. capacitance (C0) | 6.3 uF | 6.3 uF | 2.4 uF |
Max. inductance (L0) | 1 mH | ||
Fuse nominal current | 100 mA | ||
Resistance | 12.2 Ohm | 28 Ohm | 47 Ohm |
Operating temperature range | 0 to 45 °C | ||
Explosion proof marking | [Exia]IIA | ||
Weight, max. | 0.02 kg |